Mount the UPS on the wall using 4 screw plates. Remove the UPS cover by unscrewing the screws on the door.
Disconnect the Phoenix socket on the control panel and connect the 8 ter- minals of the UPS socket to the control panel based on the UPS wiring dia- gram. Please note that S2 and S must be same phases, unless control panel fault UPS–5 S2<–>S will be displayed.
Connect the LAN cable (available inside UPS) to UPS socket in LIGHT controller inside control panel.
Turn ON the control panel after making sure about connections. Choose “Main Setting” group in “All Parameters” menu and “Enable” the “Rescue” parameter. Light Controller: All Parameters / Main Settings/ Rescue = Enable
Connect BAT miniature fuse in UPS and close the cover of UPS with screws.
If the UPS works properly, the UPS LED which is located on top of LAN connection flashes